Infatuation Rules
Photo by RODNAE Productions Pexels Logo Photo: RODNAE Productions

Why is Romex not allowed in conduit?

one reason you don't put romex in conduit is because it creates more heat and is not advised in conduit if you have conduit you can run insulated wires instead it's probably cheaper. when you put romex inside conduit The Romex cannot breathe and retains too much heat.

How a guy falls in love?
How a guy falls in love?

Men Who Fall In Love With Women That He Knows He Makes Happy In this case, happiness means something more. Many men fall by spending time with a...

Read More »
What is the best age difference for married couples?
What is the best age difference for married couples?

1 to 3 years Couples with an age gap of 1 to 3 years (with the man older than the woman) were the most common and had the greatest levels of...

Read More »

In addition to Tester101's excellent answer on when NM-B can be run through conduit, there is a section in the NEC which indirectly prohibits running NM-B through conduit in specific scenarios: From the 2014 NEC: 312.5 Cabinets, Cutout Boxes, and Meter Socket Enclosures. Conductors entering enclosures within the scope of this article shall be protected from abrasion and shall comply with 312.5(A) through (C). (C) Cables. Where cable is used, each cable shall be secured to the cabinet, cutout box, or meter socket enclosure. Exception: Cables with entirely nonmetallic sheaths shall be permitted to enter the top of a surface-mounted enclosure through one or more nonflexible raceways not less than 450 mm (18 in.) and not more than 3.0 m (10 ft) in length, provided all of the following conditions are met: (a) Each cable is fastened within 300 mm (12 in.), measured along the sheath, of the outer end of the raceway (b) The raceway extends directly above the enclosure and does not penetrate a structural ceiling. (c) A fitting is provided on each end of the raceway to protect the cable(s) from abrasion and the fittings remain accessible after installation. (d) The raceway is sealed or plugged at the outer end using approved means so as to prevent access to the enclosure through the raceway. (e) The cable sheath is continuous through the raceway and extends into the enclosure beyond the fitting not less than 6 mm (1⁄4 in.). (f) The raceway is fastened at its outer end and at other points in accordance with the applicable article. (g) Where installed as conduit or tubing, the cable fill does not exceed the amount that would be permitted for complete conduit or tubing systems by Table 1 of Chapter 9 of this Code and all applicable notes thereto. Informational Note: See Table 1 in Chapter 9, including Note 9, for allowable cable fill in circular raceways. See 310.15(B)(3)(a) for required ampacity reductions for multiple cables installed in a common raceway. The fittings used with NM cable to enter a breaker panel also secure the cable to the panel. When conduit is used, I am not aware of another approved method to secure the cable to the breaker panel as required for conduit runs longer than 10 ft. So practically speaking, you cannot have an entire run of NM-B (or any other non-metallic sheathed cable assembly) enclosed in conduit from a breaker panel because it then limits you to a maximum length of 10ft from a surface-mounted cabinet, cutout box, or meter socket enclosure (including breaker panels/boxes in their definitions). The only direction that NM-B can exit the panel in conduit is out of the top of the panel. The conduit for runs attached directly to the surface-mounted panels also have to be a nonflexible conduit per this clause as well. I believe flexible conduit is out of the picture because it offers no protection from physical damage anyways and that is the primary practical reason to run NM-B in conduit, so you might as well be directly attaching the cable to the breaker panel. This clause also implies that runs of NM-B fully enclosed in conduit attached to a recessed-mount panel are prohibited. I believe this is the same reason that non-flexible conduit is not specified because NM-B should be protected from damage by the wall covering anyway for a recess-mount panel and there is no longer need for non-flexible raceways to protect the cable.

How do boys glow up?
How do boys glow up?

Tips To Get Glowing Skin For Men Cleanse your face before going to bed. ... Wash your face before starting your day. ... Exfoliate twice/thrice a...

Read More »
What is a situationship mean?
What is a situationship mean?

Less than a relationship, but more than a casual encounter or booty call, a situationship refers to a romantic relationship that is, and remains,...

Read More »

What is orange buried cable?

The line is known as a drop. Temporary drops are typically orange. Techs will sometime run temporary drops so customers don't need to wait for service. The drops are not dangerous to touch, so if you need to move the drop it's fine to do so. Temporary drops are usually buried by a special crew within 10 business days.

***Created by our Community Experts***

Don't panic! A crazed Comcast technician hasn't lost his/her marbles. The line is known as a drop. Temporary drops are typically orange. Techs will sometime run temporary drops so customers don't need to wait for service. The drops are not dangerous to touch, so if you need to move the drop it's fine to do so. Temporary drops are usually buried by a special crew within 10 business days. The process may take longer in some cases, but it shouldn't be very much longer than a few weeks. If the ground is frozen where you live, Comcast won't be able to bury the drop until spring. The actual process of getting the drop buried will very by state. In some regions the crew will just lift up your sod, place the cable underneath and replace the sod. Other installations can be more complicated. For instance, if the crew needs to run your drop under a sidewalk or driveway. You may see flags and paint in your yard before the drop burial, those indicators are required by law so the bury crew does not come in contact with other underground utilities. There is no cost to you to replace/bury a drop and your yard will be restored to its original state once the drop is buried. Occasionally there is a mix up and Comcast forgets to bury the drop. If this has happened to you, please post in the Customer Service forum. Title your post "There is an orange cable in my yard" or maybe "Please bury my drop". An actual Comcast employee will give you individual attention and make sure your drop gets buried.

Why is my girlfriend always picking fights?
Why is my girlfriend always picking fights?

If your girlfriend is constantly picking fights, know that it's because she's picking up on something. It might not be about your messy room or...

Read More »
What colors are considered seductive?
What colors are considered seductive?

RED, PINK, ORANGE, YELLOW. Strong, bold, and daring. Anything red is always hot and dangerous… and very sexy! ... BLUES AND GREENS. You can't get...

Read More »
Why do girls stay in toxic relationships?
Why do girls stay in toxic relationships?

She may stay because she grew up in a family where abuse was normal, making it hard to recognize when a relationship is unhealthy. She may stay...

Read More »
How long does it take for him to miss me during no contact?
How long does it take for him to miss me during no contact?

In fact, based on our research you can expect the average ex to begin missing you anywhere between 2.5 to 5.2 months after a breakup assuming you...

Read More »